Selection of MCCB on main line
(2) Starting current and starting time
(3) Selection
a. When the starting time is relatively short
(1) When the loads are motors, etc.
When
motors, etc. are connected to the main line, MCCB rated current shall be less
than the value obtained by multiplying the sum of rated currents of the motors
by 3 and adding the sum of the rated currents of other loads to the tripled
sum. However, when the sum total exceeds 2.5 times the allowable current of the
main line, the rated current shall be less than the value obtained by
multiplying the allowable current by 2.5. If the allowable current of the main line
exceeds 100A and the value does not conform to the standard rating of any MCCB,
it is allowed to select the rating just above the value. Actually, select MCCB
in accordance with the following procedures. Divide the loads on the branch
circuits into groups of motors which will start simultaneously. Regard each
motor group as one motor (hereinafter, referred to as a synthesized motor)
which has the total full-load current of the full-load currents of the motors
in the group, and the synthesized motors will start successively. Determine the
rated current of the circuit breaker for the branch circuit of each synthesized
motor. The maximum rated current is IB max. When the
full-load currents of other synthesized motors is I1, I2 ···· In-1, the
rated current IB of main
line circuit breaker can be obtained by the following formula.
IB = IB max + (I1 + I2 + ······· + In-1) 3 D
D is the demand factor, and, if it is unknown,
it is regarded as 1.
(2)When loads are only lamp and heater circuits
MCCB
rated current shall be less than the allowable current of the main line and determined
by multiplying the sum total of the rated currents of MCCB on each branch
circuit by the demand factor.
Selection of MCCB for lamp or heater branch circuit
The
lamp and heater circuits refer to circuits on which the starting current and
starting time are not so significant that the operation of MCCB is affected.
For lamp circuits for mercury lamps, etc. which have rather large starting
current 3
long starting time, select MCCB in accordance
with the procedures for motor circuits. It is better to allow a margin between
the load current of lamp or heater circuit and the rated current of MCCB for
the following reasons.
1) MCCB are designed to protect wires on the outside of panels
according to the temperatures in the panels. Generally, MCCB are adjusted based
on an ambient temperature of 40°C. If the estimated maximum temperature in a
panel is higher than 40°C, it is better to reduce the load at a rate of 1% per
difference of 1K.
2) In addition, it is better to allow a margin of 10 to 15% separately
from the margin stated (in the above point) in consideration of difference between nominal value and actual
value of full-load current of load device, increase in full load current due to
deterioration of load device and fluctuation of supply voltage and frequency.
Selection of MCCB for motor branch circuit
When
selecting the rated current of MCCB for a motor branch circuit, it is necessary
to take into consideration that considerably larger transient currents, such as
starting current and starting inrush current, than the full-load current will
flow. Select MCCB rated current to prevent operation of MCCB due to these
starting transient characteristics. The relationship between them is shown in
Fig. 5. 2.
(1) Starting inrush current
The
starting inrush current reaches the maximum value in 1/2 cycle after power is
applied and then rapidly attenuates. The starting inrush current was explained
in detail in “Protection Coordination” of 4. 5. 3 and 4. 5. 4. If the starting inrush
current enters the operating range of the instantaneous tripping element of
MCCB, MCCB will trip. Select MCCB which has an instantaneous tripping current higher
than the starting inrush current depending on the starting method.
a. In the case of full voltage starting (direct-line starting)
Starting
inrush current owing to superposition of transient current caused by low power
factor of starting current and reduction of motor impedance caused by
saturation of magnetic path may lead to incorrect operation of MCCB. To prevent
the incorrect operation, the instantaneous tripping current of MCCB must be approx.
12 times higher than the full-load current.
b. In the case of star-delta starting
If
the phase of residual voltage is reversed to the phase of supply voltage on an
open transition system, starting at the supply voltage corresponds to starting
at overvoltage, and the power factor of current upon switching is improved compared
to that upon starting in the stopped state. However, to prevent incorrect
operation caused by starting inrush current owing to superposition of transient
current, the instantaneous tripping current of MCCB must be approx. 17 times
higher than the full-load current. On a closed transition system, the instantaneous
tripping current of MCCB is allowed to be almost equal to that in the case of direct-line
starting.
c. In the case of instantaneous restarting
As
in the case of star-delta starting, if the phase of residual voltage is
reversed to the phase of supply voltage, starting at the supply voltage
corresponds to starting at overvoltage, and inrush current flows. The
instantaneous tripping current of MCCB must be approx. 19 times higher than the
full-load current.
d. Plugging
Since
there is a phase shift of 120° between residual voltage and supply voltage,
starting at the supply voltage corresponds to starting at overvoltage, the
power factor reduces considerably, and large starting current flows. The instantaneous
tripping current of MCCB must be approx. 29 times higher than the full-load
current.
(2) Starting current and starting time
The
multiplying factors stated in a, b and c apply in the case where the starting
current is 8 times the full-load current. The duration of starting current is
affected by the inertia moment of load. Generally, for standard motors, if the starting
time is less than 15 s, they are considered to be improper when the safety time
exceeds 15 s.
(3) Selection
Concretely,
select MCCB in accordance with the following procedures.
a. When the starting time is relatively short
When
the starting current is 600% and the starting time is within 2 to 3 s, a motor
breaker can be used. However, the scope of protection is limited depending on
the device to be protected as shown in Table 5. 2.
b. When the starting time is relatively long
When the starting current is 600% and the starting time is within 10 s,
apply a combination starter method with MCCB and magnetic switch.
No comments:
Post a Comment