This system uses the same principle of duplicate
sources from the power supply point using two primary main breakers and a
primary tie breaker. The two primary main breakers and primary tie breaker
being either manually or electrically interlocked to prevent closing all three
at the same time and paralleling the sources. Upon loss of voltage on one
source, a manual or automatic transfer to the alternate source line may be used
to restore power to all primary loads.
Each transformer secondary is arranged
in a typical double ended unit substation arrangement as shown in Figure 1.1-37. The two secondary main breakers and
secondary tie breaker of each unit substation are again either mechanically or
electrically interlocked to prevent parallel operation. Upon loss of secondary source
voltage on one side, manual or automatic transfer may be used to transfer the
loads to the other side, thus restoring power to all secondary loads.
This
arrangement permits quick restoration of service to all loads when a primary feeder
or transformer fault occurs by opening the associated secondary main and
closing the secondary tie breaker. If the loss of secondary voltage has
occurred because of a primary feeder fault with the associated primary feeder breaker
opening, then all secondary loads normally served by the faulted feeder would
have to be transferred to the opposite primary feeder.
This means each primary
feeder conductor must be sized to carry the load on both sides of all the
secondary buses it is serving under secondary emergency transfer If the loss of
voltage was due to a failure of one of the transformers in the double-ended
unit substation, then the associated primary fuses would open taking only the failed
transformer out of service, and then only the secondary loads normally served
by the faulted transformer would have to be transferred to the opposite
transformer.
In either of the above emergency conditions, the in-service
transformer of a double-ended unit substation would have to have the capability
of serving the loads on both sides of the tie breaker. For this reason,
transformers used in this application must have equal kVA ratings on each side
of the double-ended unit substation. The transformers are sized so the normal
operating maximum load on each transformer is typically about 2/3 base
nameplate kVA rating.
Typically these transformers are furnished with
fan-cooling and/or lower than normal temperature rise such that under emergency
conditions they can continuously carry the maximum load on both sides of the
secondary tie breaker. Because of this spare transformer capacity, the voltage
regulation provided by the double-ended unit substation system under normal
conditions is better than that of the systems previously discussed.
The double-ended
unit substation arrangement can be used in conjunction with any of the previous
systems discussed, which involve two primary sources. Although not recommended,
if allowed by the utility, momentary re-transfer of loads to the restored source
may be made closed transition (anti-parallel interlock schemes would have to be
defeated) for either the primary or secondary systems.
Under this condition,
all equipment interrupting and momentary ratings should be suitable for the
fault current available from both sources.
For double-ended unit substations equipped
with ground fault systems special consideration to transformer neutral grounding
and equipment operation should be made—see Grounding/Ground
Fault Protection
section of this Design Guide. Where two single-ended unit substations are
connected together by busway or external tie conductors, it is recommended that
a tie breaker be furnished at each end of the tie conductors. The second tie
breaker provides a means to isolate the interconnection between the two single-ended
substations for maintenance or servicing purposes.
Figure 1.1-37. Two-Source Primary—Secondary Selective System |
No comments:
Post a Comment