Magnetizing inrush current of transformer
When
power is turn on to a transformer, significantly largemagnetizing current may
flow into the transformer. The magnetizing current may have a peak value of 10
times or more the rated current and may cause malfunction of MCCB, and the
transformer circuit may not be closed. This current is called magnetizing
inrush current.
The magnetizing inrush current varies depending on at which
circuit voltage the transformer has been turned on and in which state the core
residual magnetic flux was. The magnetizing inrush current is maximized when
the transformer is turned on at point P in Fig. 5. 6. The magnetic flux changes
by 2ᴓm in 1/2 cycle after the transformer is turned
on. Since the magnetic flux starting point is the residual magnetic flux fr in the center of the core before the transformer is turned on, the
magnetic flux will be 2ᴓm + fr after 1/2 cycle and considerably exceed the saturated magnetic
flux of the core, and, as the result of this, large magnetizing current will
flow. This magnetizing inrush current attenuates with time. There is a tendency
that the higher the transformer capacity, the larger the attenuation time
constant. Table 5. 9 shows the approximate values of magnetizing inrush
current. The values shown in Table 5. 9 are larger than the actual magnetizing
inrush current values because the values were determined not in consideration
of current limiting due to electric circuit impedance. If the value is unknown,
the value in Table 5. 9 should be used. It is recommended to refer to the
transformer manufacturer for details.
Notes
- Multiple: The first peak value of magnetizing inrush current for rated current peak value.
- Since the magnitude of magnetizing inrush current considerably depends on the applied voltage, making phase and residual magnetic flux of core, normally, the magnetizing inrush current changes every time a transformer is turned on. The above table shows the maximum values. Note that the magnetizing inrush current caused when the rated voltage is applied to the rated tap may be larger if overvoltage is applied.
Selection of MCCB for primary side of transformer
The
magnetizing inrush current stated in 5. 4. 1 attenuates with time, and, lastly,
only the magnetizing current flows. However, the instantaneous trip of MCCB
reacts to transient current. Therefore, it is necessary to select MCCB having sufficiently
higher instantaneous tripping current than the magnetizing inrush current of
transformer. Thermal magnetic MCCB are more suitable than hydraulic magnetic
MCCB because thermal magnetic MCCB with high magnetic tripping current can be
manufactured easier. Example of selection of MCCB for primary side of 3-phase 420V
50 kVA
The
rated current I (RMS value) can be obtained as shown below.
The
magnetizing inrush current peak value Iᴓ
is 22 times the rated current peak value.
Accordingly,
MCCB having an instantaneous tripping current peak value of 2137A or more
should be selected.
select the model which respective to the instantaneous tripping current peak value.
Follow below instructions to know the instantaneous tripping current peak value of model at 150A.
Therefore this model meet the requirement.
No comments:
Post a Comment