Branch circuits
Branch
circuits are closest to devices and operators and, therefore, involve a high
risk of electric hazard. Except for special cases, the use of high-sensitivity
circuit breakers (30mA or so) is desirable. For outlets in western style
bathrooms, vending machines, machines using midnight power and mobile and
portable motor-driven machines, high-sensitivity high speed circuit breakers
should be used. Generally, since branch circuits are shorter and have lower
earth floating capacitance, the risk of unnecessary operations is low even if
high-sensitivity circuit breakers are used. However, if the earth floating
capacitance is increased, it is better to reduce the constant leakage current
through improvement of branch wiring method and use high-sensitivity circuit
breakers. Under some conditions, it is difficult to use high-sensitivity
circuit breakers. In such a case, as stated in 9. 2. 2 “Selection for electric
shock protection for general equipment,” use medium sensitivity circuit
breakers with sensitivity of 100mA, 200mA or 500mA reducing the class D
grounding resistance value to prevent the voltage from exceeding the allowable
contact voltage.
Main circuits
ELCB
installed on main circuits shall be capable of providing selective coordination
with ELCB on branch lines and protecting the electric circuits from ground
fault of the main lines. The most common and simplest method is to use medium
sensitivity time delay ELCB, and this method is economical. Note that since the
rated non-operating current of ELCB is 50% of the rated current sensitivity,
the rated current sensitivity of ELCB for branch exceeds the rated
non-operating current of ELCB for main line if the rated current sensitivity of
ELCB for branch is too close to that of ELCB for main line, and selectivity
cannot be obtained. Therefore, the current sensitivity of branch and that of
main line shall be different desirably by 2.5 times. Table 9. 8 shows the
relationship between rated current sensitivity of ELCB for branch circuit and
that for main circuit.
Table 9. 8 Relationship between rated current sensitivity of ELCB for branch circuit and that for main circuit |
Detection of ground fault by ground wire
One
of the methods for protecting the whole electric circuit from ground fault is
detection of ground fault by ground wire. As shown in Fig. 9. 26, only the
ground wire of power supply is passed through the ZCT. When the circuit is
broken, it is protected by the earth leakage relay combined with MCCB with SHT.
Fig. 9. 26 Ground fault protection by ground wire |
Arc welder circuits
In
many cases, an arc welder is moved in a working site during use. Therefore,
there is a possibility that the workers may touch the insulated wires or
movable cables on the primary side. In such a case, it is desirable to install
ELCB. Therefore, ELCB are used in many cases. ELCB for arc welders must not
malfunction with an instantaneous transient phenomenon at the start of arc
welding. Therefore, some manufacturers separate the circuit breakers for arc
welders from others. Mitsubishi ELCB of
Fig. 9. 27 Arc welder circuit
standard
type can be used for arc welders. There are various kinds of welders, including
arc welders and resistance welders. On welder electric circuits, as shown in
Fig. 9. 27, the low-voltage circuit (primary circuit of welder transformer) is
grounded, and the load circuit of the welder (secondary circuit of welder
transformer) is insulated from the primary side. When ELCB is installed on this
low-voltage circuit, ELCB can protect only the range to the primary side of the
welder transformer from electric shock and cannot protect the secondary circuit
because the circuit is insulated from the primary side.
Fig. 9. 27 Arc welder circuit |
For example, if
insulation breakage occurs between the primary winding of the welder
transformer and outer case, the “welder transformer / outer case /
protective ground wire / earth / electric circuit ground wire / transformer” circuit will be formed as shown in Fig. 9. 27, and
ground fault current will flow to operate ELCB. However, even if the welding
rod or workpiece is connected to the earth, ground fault current will not flow
to the electric circuit ground wire because the primary side and secondary side
of the welder transformer are insulated.
Therefore,
it is unnecessary to take into consideration the leakage current which will be
generated if the workpiece is connected to the earth, and ELCB rated current
sensitivity of 30mA is allowed. However, when one ELCB is installed for tens of
welders or the wire between ELCB and welder is remarkably long, it may be
desirable to install ELCB with medium sensitivity (200 or 500mA) in
consideration of the earth floating capacitance. The secondary circuit of the
arc welder transformer has a voltage of about 70V while welding is suspended
and can cause electric shock. Therefore, measures against electric shock must
be taken for the circuit. To prevent the electric shock, an electric shock
preventive device should be installed. The electric shock preventive device
keeps open the primary side of the welder transformer while welding is
suspended. Therefore, there is no possibility of electric shock on the
secondary side. During welding, the voltage between welding rod and workpiece
is reduced to several V, and there is no risk of electric shock.
✦Points for selection
(1)
Operation with overcurrent trip element
The
instantaneous tripping current value must be set larger than the transient
inrush current value of welder. The transient inrush current values of
commercially available welders are 8 to 9 times. (2) Operation with earth
leakage trip element Voltage may be generated on the secondary side of ZCT by
the transient inrush current of welder, and a phenomenon similar to ground
fault may occur. Mitsubishi MCCB have excellent resistance to such transient
phenomenon (equilibrium characteristics), and even the standard models will not
malfunction.
Fig. 9. 28 Overcurrent tripping characteristics of ELCB |
(3)
Rated current
Generally,
calculate the rated current by the following formula in consideration of the
use at the maximum output.
(4)
Rated current sensitivity
Since
the major purpose is protection from electric shock, it is recommended to
select a circuit breaker with rated current sensitivity of 30mA. However, when
the electric circuit is remarkably long, determine the rated current
sensitivity carefully because a circuit breaker may malfunction owing to the
earth floating capacitance of the electric circuit.
In
this case, calculate the current sensitivity by the following formula.
Resistance welder circuits
Resistance
welders are classified into several types according to voltage and capacity.
All resistance welders used at 400VAC shall be provided with ELCB, and those used
at 200VAC shall be provided with ELCB if they are water cooled and may be
exposed to moisture. In the case where workers may touch insulated wires or
movable cables of welders, ELCB shall be installed on the welders used at 200VAC
and 400VAC. Fig. 9. 29 shows an example of a resistance welder circuit. Also on
this circuit, ELCB can protect only the range to the primary side of the welder
transformer from electric shock and cannot protect the secondary circuit.
However, the voltage on the secondary side is normally 8V or so, and there is
no possibility of electrocution at this voltage. (It is said that voltage of
25V or less is safe even in a sweating state.) Mitsubishi ELCB (NV225-WEP and
NV400-WEP) have builtin timers and can protect circuits even from abnormal weld
flow.
Fig. 9. 29 Resistance welder circuit |
When
welding is started, the timer detects the welder current and starts counting
the time. If the welder current continues to flow after a lapse of the welding
time set on the timer (continuous arc-through or abnormal weld flow), the
built-in contact in the timer will close, the tripping coil will be excited,
and the circuit breaker will automatically trip. In the case of normal weld
flow, the welder current will be stopped within the welding time set on the
timer, and the timer will be reset (the maximum reset time is 0.1 sec) and get
ready for start of next welding. The welding time shall be set on the timer
somewhat longer than the welding time set on the welder control unit. When
earth leakage occurs, the ZCT will detect the leakage, the tripping coil will
be excited through the leakage detector, and the circuit breaker will trip. At
a welder circuit a large inrush current will flow owing to the transient
phenomenon at the start of welding, and the ZCT may detects it as earth leakage
and cause malfunction (the magnitude of inrush current at which the circuit
breaker does not malfunction is indicated as the RMS value referred to as an
equilibrium characteristic). Mitsubishi ELCB have an equilibrium characteristic
improved by reinforced magnetic shield and will not malfunction. When short
circuit occurs, the instantaneous trip device will function, and
instantaneously the circuit breaker will trip automatically.
✦Points for selection
(1)
Selection of rated flowing current
The
rated flowing current is 225A or 400A. Select the current based on the
thermally equivalent current of the welder primary current. Actually, the
welder primary current varies depending on the welding conditions, such as the
material and thickness of workpiece. However, the welder primary current
determined based on the current value obtained from the rated capacity of
welder can be used without problem. Since the rated capacity of welder is prescribed
as input at a service factor of 50%, the thermally equivalent current Ie can be
obtained by the following formula.
Where,
P is the rated capacity of welder, V is the rated voltage of welder, and beta
is the service factor and expressed by the formula
beta = weld time/weld cycle.
For
example, when the rated capacity is 100kVA and the rated voltage is 415V:
The
rated flowing current is determined by allowing a margin of about 15% for this
value in consideration of supply voltage fluctuation. Therefore, 170A 3 1.15 = 19A, and a circuit breaker with rated flowing current of 225A
should be selected.
Table 9. 10 Rated current sensitivity and maximum electric circuit length (m) |
(3)
Setting of instantaneous tripping current
The
instantaneous tripping current must be determined in consideration of the
maximum input current of welder and the inrush current at the start of welding.
The maximum input current can be obtained from the standard maximum input of
welder, but, when the welder secondary side is completely shorted, the maximum
input current will be higher by about 30% than the current value determined
from the standard maximum input. Therefore, the instantaneous tripping current
Iinst in consideration of the inrush current at the start of welding can be
determined by the following formula.
Note:
In the above table, the instantaneous tripping current values determined based
on inverter welder specifications are shown. When selecting the instantaneous
tripping current, it is necessary to ensure the coordination so that the surge
current capacity of control element (thyristor stack) is not exceeded.
Table
9. 9 shows the relationship between welder rated capacity and rated flowing
current of ELCB determined by the above calculation formulas.
(2)
Selection of rated current sensitivity
The
standard current sensitivity of ELCB for inverter welders is 30mA. If the
electric circuit between ELCB and welder is increased, ELCB may malfunction
under the influence of earth floating capacitance. It is necessary to install
ELCB in such a way that the circuit length is less than the value shown in
Table 9. 10. For cases where the circuit length is longer and circuit breakers
with sensitivity of 30mA cannot be used, 100mA, 200mA and 500mA circuit
breakers are available as special models.
Where,
Pmax is the standard maximum input of welder, V is the rated voltage of welder,
and K is the margin ratio for
inrush cur rent and 1 to 1.5 for models with synchronous peak control, 1.4 to 3
for models without synchronous peak control and 2 to 6 for models with
asynchronous soft start. Table 9. 11 shows examples of selection of
instantaneous tripping current determined by the above formula.
No comments:
Post a Comment