Typical
loads are shown, however, for the various motors being fed out of motor control
center MCC-DF3A. Each motor’s designation and full load amps are shown below
the motor symbol that contains the motor’s horsepower rating. Safety switch
symbols are shown between the MCC and the motor symbol. Safety switches are
used to electrically isolate the motor during maintenance or to ensure it does
not start unexpectedly when personnel are working on or in the equipment it is
powering. The operating handles of safety switches have provisions for applying
a lock-out tag-out device. They are generally provided with fuse protection to
ensure adequate short-circuit ratings for the application. For those situations
requiring a shortcircuit rating of 10 kA or less, a non-fused safety switch may
be specified.
Motor
control centers are used to group overcurrent protection and different starter
types for the motors in a portion of a power system. They may also contain associated
control and distribution equipment as well as connectivity interfaces to
industrial control or Building Management Systems (BMS). Motor starters, and
motor protective overload relays are available in both electromechanical and
electronic solid-state configurations. In a motor control center application, the
starter is provided with either a thermalmagnetic circuit breaker or high
magnetic circuit protector (HMCP) selected to permit the high inrush current of
the motor while starting. Either type of overcurrent protective device provided
must be selected to coordinate with the motor overload protection relay. This
combination starter is mounted in a removable “bucket”. Lower ampacity buckets
are wired to stabs on the rear of the bucket and manually plugged directly onto
the vertical power bus bars in the MCC.
Note: Larger hp starter sizes may be physically
hardwired to the bus.
Eaton’s
FlashGardE motor control center “bucket” shown in Figure 1.1-14 adds an
additional level of personnel safety. The FlashGard design incorporates a RotoTract™
lead screw assembly that withdraws the stab assembly off the energized bus bars
and into the bucket. A spring-loaded shutter then automatically closes off
access to the bus bars.
Figure 1.1-14. Freedom FlashGard FVNR Starter |
The
75 hp Circulating Water Pump motors CWP1 through CWP4 shown in Figure 1.1-13are examples of full voltage non-reversing starters (FVNR). The drawing
documents these as having a full load amp (FLA) rating of 96 A. Based on rating
of 96 A (75 hp), which would require a NEMA Size 4 combination starter. The
starter symbol shown on the drawing includes a normally open contactor. This is
followed by an overload relay symbol. The overload relay measures the current flowing
through the starter contacts to the motor and calculates when an extended overload
condition is present that will damage the motor. A contact from the overload
relay is wired into the control circuit of the starter, which deenergizes the contactor
coil in the event of an overload. Electromechanical overload relays sense an overcurrent
by directing the current through a melting eutectic element or a heater pack.
The heat is proportional to the amount of current flowing. When the eutectic
element melts or the bimetal bends due to the heat from the heater pack, the
relay opens the control circuit. The “SSOL” nomenclature next to the overload relay
shows these particular starters as having solid-state overload relays. The text
“W/GFP” calls for ground fault equipment protection. In the past, this would
have had to be added as a separate relay, however, many of the new overload
relays use microprocessors to monitor a number of variables including voltage
to the motor. Eaton’s C440, C441 and C445 all include phase loss and ground
fault protection.
Eaton’s
solid-state overload relays also have the ability to communicate status
including current per phase and other key operational variables back to a control
system. Motors are available in a number of winding styles and performance characteristics.
The 75 hp CT-1 through CT-4 motors shown fed from MCC-DF3A are of the
two-speed, two-winding variety. Note that six-pole disconnects are required for
two-speed, two-winding motors. Because the cooling towers are typically located
outdoors on a roof, a NEMA 3R drip-proof safety switch would be required. Many
two-speed starters are applied on motor loads such as cooling towers, where the
fan needed to run at a lower speed or higher speed, to optimize the heat
transfer and maintain water temperature in the return supply to the chiller. ASHRE
90.1 is recommending the use of variable frequency drives in applications where
they can reduce energy consumption and improve the performance of the equipment
they are powering. As an example, in lieu of two-speed motors on cooling
towers, VFDs are being used to maximize efficiency of the cooling process. In
these cases, a sensor is placed in the wet well of the cooling tower to monitor
the temperature of the water. A set-point controller in the VFD utilizes the
output signal from a sensor mounted in the return water pan as feedback to
modulate the speed of the fan.
The
150 hp CHWP-1 and CHWP-2 chilled water pumps in MCC-DF3A are shown being fed from
solid-state reduced voltage starters (SSRV). These SSRV starters reduce the
motor inrush and ramp them up smoothly to their full running speed. SSRV
Starters can be used to reduce the “water hammer” effect where the pipes in the
system experience a sudden thrust of pressure. Recent declines in the cost of
VFDs and their associated energy savings capability have led to their growing
popularity in a number of HVAC applications. While VFDs still have a higher initial
purchase cost than standard starters or solid-state reduced voltage starters,
they have a relatively short payback period. A savvy building owner and design
engineer will recognize that the total cost of ownership and energy savings
must be considered when electing to specify VFDs.
The
output voltage and frequency of this VFD can be set by a digital signal from
the keypad or an external analog signal such as 4–20 mA. A set-point controller
in the VFD can also be used to maintain a temperature, flow rate or pressure
level by utilizing an external feedback signal from a sensor. The use of VFDs
in heating, ventilating, air conditioning (HVAC) has been popularized due to
the VFD’s ability to save energy. When motors on centrifugal fans and pumps are
operated at reduced speeds, the energy required to produce the torque at motor’s
output shaft is reduced by the cube of the speed. See Eaton Application Paper
IA04003002E for details.
This
type of centrifugal load is best served by a variable torque VFD that optimizes
the volts per hertz relationship throughout the speed range. In addition to the
dramatic energy savings that can be experienced below 80% of the motor’s base
speed, VFDs ensure a soft motor start and acceleration throughout the speed
range. Eaton’s CPX Clean Power (18 Pulse) VFDs are available in low voltage for
operation with 208 V, 230 V, 480 V and 575 V motors.
No comments:
Post a Comment