Wednesday 5 February 2020

Earth leakage tripping device


(1) ZCT (zero-phase current transformer)
The ZCT is a current transformer for detecting minute ground fault current and shall be distinguished from general current transformers (CT). For the ZCT, mainly permalloy, a special material with high magnetic permeability, is used. It consists of a permalloy core, a primary conductor which feeds the main circuit current and a secondary winding on the core. The magnetic fluxes generated by the currents of the phases of the primary conductor are vector synthesized by the core, and electromotive force is generated on the secondary winding by the magnetic flux according to the difference among the magnetic fluxes of the phases. Therefore, if the vector-synthesized current of the phases is 0, the magnetic fluxes cancel with one another in the core, and electromotive force is not generated on the secondary winding regardless of the magnitude of the primary current. On the other hand, if a ground fault occurs, the current balance among the phases is disturbed, the core is excited by the magnetic flux corresponding to the magnitude of the ground fault current, and electromotive force is generated on the secondary wiring.


(2) Electronic circuit
The circuit diagram is shown in Fig. 7. 5. The control power of almost all ELCB is 100 to 440VAC for facilitating selection, storage and maintenance. In addition, models with 100 to 200VAC, 100 to 230VAC, 200 to 415VAC and 200 to 440VAC and with fixed voltage of 100VAC are available.


1Detection of ground fault on secondary side of inverter
As an example method of detecting the ground fault current on the inverter primary side and secondary side with ELCB installed on the inverter primary side, below is explained the method of detecting ground faults on the inverter secondary side where the waveform distortion is the largest.
a. Spectrum of leakage current on inverter secondary side
Fig. 7. 6 shows the spectrum (200V, Δ connection, one-line grounding, the same hereinafter) of ground fault current caused by the resistance on the inverter secondary side in the case of use of Mitsubishi inverter FR-Z220. The spectrum consists of commercial frequency, inverter operation frequency and carrier frequency components and their harmonic components. The spectrum contains commercial frequency and inverter operation frequency components at the same rate as that of the content of carrier frequency components. Fig. 7. 7 shows the spectrum of ground fault current on the inverter secondary side including the leakage current caused by earth capacitance in the case of use of FR-Z220. This example simulates a case where the electric circuit on the inverter secondary side is long and its earth capacitance is large. Since the earth impedance caused by capacitance is inversely proportional to the frequency, the content of harmonic components in the carrier is higher compared to in Fig. 7. 6. This content increases in proportion to the earth capacitance and carrier frequency. The content of commercial frequency and inverter operation frequency components is identical to that in Fig. 7. 6.




b. Concept of detection of ground fault on inverter secondary side
To detect ground fault on the inverter secondary side, it is necessary to reduce the influence of leakage current caused by earth capacitance on the secondary side. For this purpose, we used a method to remove the carrier frequency and harmonic content of the carrier which change depending on the earth capacitance and may cause unnecessary operations and unstable sensitivity current with a low pass filter. The filter characteristics are shown in Fig. 7. 7. IEC 60479-2 presents the frequency characteristics of current value at which ventricular fibrillation is caused by the current passing the human body shown in Fig. 7. 8. This curve shows that, at frequencies higher than 1kHz used as the inverter carrier frequency, the current value at which ventricular fibrillation occurs to expose the human body to hazardous situation is 14 times or more the value at 50/60 Hz and there is a low risk of electrical shock. Therefore, it is possible to realize stable detection of ground faults while ensuring the safety of human body against electrical shock by removing carrier frequency and the harmonic content of the carrier upon detection and detecting ground faults based only on the fundamental wave components. On inverters, the fundamental wave content is approx. 70% in the ground fault current. This percentage is less affected by the earth capacitance and is in proportion to the magnitude of ground fault current. Therefore, stable detection of ground faults can be realized by judging based on the fundamental wave content.


c. Structure and operation of ground fault detection circuit
As the low pass filter for removing carrier frequency and harmonic components of carrier, a digital filter was used. On ELCB applicable to higher harmonics and surge, signals from the ZCT are input to the input circuit and converted from analog to digital by the A/D converter. The digitalized signals are input to the low pass filter that is a digital filter. The digital filter is used because the filter provides sharp at tenuat ion necessary for fundamental f requency components and carrier frequency (depending on the inverter type, approx. 800 Hz on low-frequency products) and filter characteristics without attenuating minute ZCT signals, and the filter constant for obtaining a low cutoff frequency can be set without influence on stability of ZCT and electronic circuit characteristics. Fig. 7. 9 shows the structure of electronic circuit, and Fig. 7. 10 shows the digital filter block diagram. The ground fault current discriminating circuit detects the magnitude of ground fault current and the duration of signal. Fig. 7. 11 shows the function block diagram for explaining the operation. When the ground fault signal level exceeds the detection level, charging of the capacitor is started, and the occurrence of ground fault is detected after a lapse of a certain time. Therefore, relatively small surge current components which are leaked by the earth capacitance are removed. These circuits are contained in one chip as an IC for ELCB. Fig. 7. 12 shows the effect of digital filter in detection of ground fault current. Comparing the waveforms before and after the digital filter, it is found that the fundamental wave components can be effectively extracted from the leakage current on the secondary side masked by the high frequency components. That is, not only on the primary side, but also on the secondary side, ground faults can be stably detected through the digital filter. However, for a circuit containing harmonic components, the filter shall be used with load device leakage current distortion of 10kHz or less and at 3A or less because the zero-phase current transformer (ZCT) of the circuit breaker is overheated by iron loss. For circuit breakers with frame size of 800A and above, it is necessary to use the filter with load device leakage current distortion of 5kHz or less and at 3A or less.




Technique for prevention of unnecessary operations caused by surge
As an example method of detectings the ground fault current on the ino higher harmonics and surge, signals from the ZCT are input to the input circuit and converted from analog to digital by the A/D converter. The digitalized signals are input to the low pass filter that is a digital filter. The digital filter is used because the filter provides sharp attenuation necessary for fundamental frequency components and carrier frequency (depending on the inverter type, approx. 800 Hz on low frequency products) and filter characteristics without attenuating minute ZCT signals, and the filter constant for obtaining a low cutoff frequency can be set without influence on stability of ZCT and electronic circuit characteristics. Fig. 7. 9 shows the structure of electronic circuit, and Fig. 7. 10 shows the digital filter block diagram. The ground fault current discriminating circuit detects the magnitude of ground fault current and the duration of signal. Fig. 7. 11 shows the function block diagram for explaining the operation. When the ground fault signal level exceeds the detection level, charging of the capacitor is started, and the occurrence of ground fault is detected after a lapse of a certain time. Therefore, relatively small surge current components which are leaked by the earth capacitance are removed. These circuits are contained in one chip as an IC for ELCB. Fig. 7. 12 shows the effect of digital filter in detection of ground fault current. Comparing the waveforms before and after the digital filter, it is found that the fundamental wave components can be effectively extracted from the leakage current on the secondary side masked by the high frequency components. That is, not only on the primary side, but also on the secondary side, ground faults can be stably detected through the digital filter. However, for a circuit containing harmonic components, the filter shall be used with load device leakage current distortion of 10kHz or less and at 3A or less because the zero phase current transformer (ZCT) of the circuit breaker is overheated by iron loss. For circuit breakers with frame size of 800A and above, it is necessary to use the filter with load device leakage current distortion of 5kHz or less and at 3A or less.



Fig. 7. 14 shows the improvement of the performance to prevent unnecessary operations of ELCB applicable to higher harmonics and surge comparing with that of a conventional model. It was confirmed that no unnecessary operation was caused in any case of gap-less surge absorber and discharge gap type surge absorber. According to the waveforms verified in Fig. 7. 14, the performance to prevent unnecessary operations is improved as stated below. (1) Resistance to leakage current caused by surge: Three times or more as peak value
(2) Leakage electric power energy (I2t) caused by surge: 100 times or more

Fig. 7. 14 Performance to prevent unnecessary operations caused by surge
Improvement of leakage protection function by type A leakage characteristics
Recently, more machines are provided with inverters and servos to improve the performance and accuracy of drive control. Inverters and servos have rectifier circuits, and if the rectifier circuits go down, leakage current with half-wave rectified waveform or phase-controlled waveform may occur. To detect this leakage current and trip the circuit breakers to prevent electric shock and fire caused by earth leakage, type A (specified by IEC 60947-2) leakage protection characteristics for detection of half-wave rectified and halfwave phase controlled waveforms of leakage current shown in Fig. 7.15 must be provided. Then, we enlarged the leakage protection range by adding a function with the type A leakage characteristics to CE-marked and UL-listed circuit breakers with frame size of 250A and smaller (except some models).



 Test device
Since electric shock may cause loss of life, it is necessary to check the operation of circuit breaker. The test device forms a ground fault simulation circuit as shown in Fig. 7. 17. Current is applied to the circuit by pressing the test button to make sure that the circuit breaker can operate surely upon occurrence of ground fault. All ELCB circuit breakers are provided with this test device.


Earth leakage indication device
After ELCB operates owing to earth leakage, the earth leakage indication button shows that it has operated not owing to short circuit caused by overload. As shown in Fig. 7. 18, the earth leakage indication button is lower than the surface in the normal state and after the circuit breaker operates owing to overcurrent, but it is protruded when the circuit breaker operates owing to earth leakage. The button is reset automatically by the handle. The button will not be damaged even if it is pushed down accidentally. Furthermore, it is designed not to hinder operation owing to earth leakage even if it is pushed down for any reason.


Trip button
Models with a trip button can be mechanically tripped by pressing this button. With an alarm switch (AL), it is possible to check the operation of the alarm circuit for tripping owing to overcurrent and, if it has an operation handle, check that the circuit breaker has been reset by the operation handle.


Sensitivity switching device
With the sensitivity switching device, the rated sensitivity current can be easily and reliably switched. Some models can switch in 3 stages, 100, 200 and 500mA, and others in 2 stages, 100 and 500mA. JIS prescribes that a device which can switch the sensitivity between high (30mA or 15mA, operation within 0.1 s) and medium (50mA to 1000mA) levels should not be provided. ELCB of 100AF and smaller do not have this device. Fig. 7. 20 shows an example of the sensitivity switching device circuit. The sensitivity can be switched by switching the adjusting resistances on the secondary size of the ZCT. The sensitivity on the high level is set by the adjusting resistance R1, and the sensitivity on the low level is set by connecting the adjusting resistances R2 and R3 in series with the switching device. This system ensures safety against contact failure between R2 and R3 owing to nonconformity of the switching device because the sensitivity current is determined by R3 and ELCB operates with high sensitivity.


Operating time switching device
The time delay circuit breakers have an operating time switching device in addition to the sensitivity switching device, which can switch the operating time to three stages, 0.45, 1.0 and 2.0 s or to two stages, 0.3 and 0.8 s. With this device, a ground fault protection coordination system can be easily configured.

No comments:

Post a Comment

Medium-Voltage Distribution System Design

A. Single Bus, Figure 1.1-40 The sources (utility and/or generator(s)) are connected to a single bus. All feeders are connected to the ...