Since
the ground fault current changes from several mA to thousands A, the selective
protection coordination shall be examined in the remarkably wide range. When a
selective breaking system is used, coordination cannot be achieved only based
on the difference in rated current sensitivity. Fig. 9.23 shows the operating
characteristics of ELCB by single lines. Selective coordination between ELCB1
with sensitivity of 30mA and high-order ELCB2 with sensitivity of 200mA can be
achieved at a ground fault current of 150mA or less. But, at a ground fault
current exceeding 150mA, there is a strong possibility that both ELCB1 and
ELCB2 will operate because they are high speed circuit breakers with operating
time of 0.1 sec or less. Therefore, the selectivity shall be examined in consideration
of the rated current sensitivity and operating time.
Fig. 9. 23 Operating characteristics of high speed MCCB |
Ground fault protection coordination by time delay circuit
breakers
In
many cases of prevention of electric shock and ground fault at terminals,
circuit breakers with high sensitivity (30mA or so) having the highest
protection effect are used. For long systems, since faults between transformer
and branches can occur, MCCB are often used also on the main lines for
protection between them. In such a case, if selective coordination is not
achieved on the whole circuit, the high order ELCB will operate upon occurrence
of ground fault, other sound circuits will be broken, and power supply cannot
be continued. Therefore, it is necessary to examine the coordination. Fig. 9.
24 shows an example of a coordination system using time delay circuit breakers,
and Fig. 9. 25 shows the coordination diagram of ELCB1, ELCB2, ELCB3 and ELCB4
on the system shown in Fig. 9. 24. If a ground fault of several A occurs at the
point A, ELCB4, which is a high speed circuit breaker, will operate within 0.1
sec. The high-order ELCB3 which is a time delay circuit breaker with operating
time of 0.3 sec has a longer operating
time than the total breaking time of ELCB4 at the branch. Therefore, selective
trip can be ensured ly. On time delay circuit breakers, the inertial
non-operating time is shown. The circuit breakers will not operate within the
time even if ground fault current is flowing. The minimum value of the time is
0.1 sec. Therefore, coordination between the time delay and high speed types
can be easily obtained as in this case.
Fig. 9. 24 Example of coordination system with time delay circuit breakers |
Fig. 9. 25 Coordination characteristics of time delay circuit breakers |
No comments:
Post a Comment