Tuesday 18 February 2020

Designing a Distribution System (Part - 2)

Standardized Drawing Symbols


The American National Standards Institute or ANSI for short, in cooperation with the Institute of Electrical & Electronics Engineers has developed standardized drawing symbols and nomenclature to represent common devices represented on one-lines, control schematics and other electrical drawings. The existing Standard for North America (including the Canadian Standard CSA Z99) is IEEE 315-1975 (Reaffirmed 1993)/ANSI Y32.2. 

This version recognizes that “Electrical diagrams are a factor in international trade: the use of one common symbol language ensures a clear presentation and economical diagram preparation for a variety of users.” Consequently, the Standards Coordinating Committee has added various International Electrotechnical Commission (IEC) symbols that are in use worldwide. 

Item A4.1.1 of IEEE 315 defines a Single-Line or (One-Line) Diagram as: “A diagram which shows, by means of single lines and graphic symbols, the course of an electric circuit or system of circuits and the component devices or parts used therein.” 

Components such as those representing circuit protective devices like fuses and circuit breakers are indicated in their most basic form. Device representations can be created by adding other componentsand nomenclature to the base component drawing. Low-voltage <1000 V circuit breakers are represented by the first two of the following symbols shown in Figure 1.1-3.

Figure 1.1-3. Circuit Breaker Symbols

Medium-voltage circuit breakers shown on a one-line typically incorporate the Basic Square Breaker symbol with the ANSI Device Number 52 inside. Medium-voltage breakers may be either fixed mount (square with device number inside) or drawout as shown in Figure 1.1-3 as well as the system one-line.

It is important to develop a naming convention so personnel working on or  responding to an event on the power system can readily identify the equipment experiencing any problems. This naming convention is also useful for those doing preventative maintenance in documenting which specific switchgear, breaker, transformer or protective relay they need to address. 

Transformers are common components of a power system and are used on both medium-voltage and low-voltage applications to step a voltage up or down to a desired level. They are available in a variety of winding configurations as detailed in the “Typical Components of a Power System” in this document.) 

Because there are many types and configurations of transformers available, it is necessary to properly document the specific requirements on the One-Line. Primary unit substation transformers are used to convert a medium voltage to another medium voltage.

Secondary Unit Substation Transformers transform a Medium Voltage to a Low Voltage Level, generally under 1000 Vac. They are available in Fluid-Filled and Dry-Type styles.

Both types of unit substation transformers can be supplied with fans to increase the transformer’s kVA ratings. Figure 1.1-4 from the mediumvoltage half of the system one-line.

The transformer’s kVA ratings are indicated at the KNAN, (Natural Air Cooled by Convection Over 300C Fire Point Fluid Filled) and KNAF (Forced Air Cooled Over 300C Fire Point Fluid Filled) ratings. 

If the transformer is described as “Delta” Primary, “Wye” Secondary configuration in the text as well as further depicted by the relationship of the “H1, H2 and H3” connections to the X1, X2, X3 and X0 symbols adjacent to it. Similarly, the verbiage in the text calls for surge and lightning protection. Symbols for the arrester and the capacitor are shown connected to the incoming terminations. Their actual ratings should be defined on the drawing or in the specifications. 

Both the transformer’s primary and secondary amps are included as a reference for sizing the conductors. This is useful to determine the quantity and size of the MV cables per NEC Article 310.60. While medium-voltage conductors are available in 90C (MV90) or 105C (MV105) ratings, the actual terminations in the transformer or switchgear cable compartments are limited to 90C. When sizing the MV cables, the NEC derating factors must also be applied depending on the type of raceway or duct bank that will be required. 

Where higher transformer secondary currents are involved, a busway flange and non-segregated busway can be supplied to connect it to the downstream MV switchgear (as shown in Figure 1.1-4). Proper selection and application of the busway requires that the rated short time and short circuit withstand current values be specified.


Figure 1.1-4. Transformer Information and Symbols


Short-circuit values are critical in the design and specification of all electrical equipment in a power system. The transformer’s Impedance, (often abbreviated as %Z) must be shown on the One-Line in order to calculate the required ratings of downstream equipment as indicated in Figure 1.1-5

It is important to remember that all transformers designed to ANSI standards have a plus and minus 7.5% tolerance for impedance. If a transformer requires an absolute minimum impedance to ensure the secondary short-circuit level does not exceed a critical value, it must be noted on the One-Line and in the accompanying project specifications. 

Consideration must also be given to the types of cable terminations based on the available short-circuit ratings. Where the available short-circuit exceeds 12.5 kA, medium-voltage molded rubber deadfront terminations are generally not an option. In these cases, the type of terminations must be specified. Stress Cone cable terminations are available in either Hot Shrink or Cold Shrink configurations. Porcelain terminators or potheads are a more expensive option, but often have higher short circuit ratings. 

Current transformers are used in both low- and medium-voltage applications as sensing devices for protective relays and meters. They are available in “donut” style, which encircle the conductor, as well as bar style, which is bolted in series with the load conductors. Both styles work on the principal of electromagnetic coupling; a current flowing through the conductor they surround induces a proportional isolated low level signal (either 1 A or 5 A) that can be measured by an electromechanical or electronic device. 

Current transformers may be shown in several formats as indicated in Figure 1.1-6

The dots, X’s or boxes are used to denote the instantaneous polarity orientation of the CT. The polarity marks on the conductor generally face toward the source of the current flow. The polarity mark on the CT winding represents the relationship of the CT’s X1 secondary terminal to the H1 medium-voltage terminal on bar type CTs or its input orientation for donut style CTs.


Figure 1.1-5. Incoming Service Calculation
NOTE: CALCULATION DOES NOT INCLUDE DOWNSTREAM MOTOR CONTRIBUTION






Figure 1.1-6. Current Transformer Symbols



In the case of Differential Protection circuits such as the 87-T1 Transformer Differential or the 87-B1 Bus Differential, the CTs are oriented in opposing directions as illustrated in Figure 1.1-7. This permits the Differential Relays to measure the current going into a transformer or bus bar and deduct the current flowing out of it. When more current is flowing into the zone of protection than is proportionally flowing out, the relay senses the “differential” and trips the circuit breakers at high speed to protect against a fault anywhere in the zone. Note the “Y” symbol, as well as the quantity “(3)” next to the CTs. This represents three CTs configured in a three-phase grounded wye arrangement. While most of the CTs on the system one-line on Page 1.1-8 are shown this way, the CTs on the output side of the 2000 A breaker S1A are not grounded.  This is done to indicate to the equipment manufacturer or installing contractor that the CT inputs to the relay should not be grounded in more than one location. CTs generally are wired to shorting terminal blocks as indicated by the “SB” in the box shown in Figure 1.1-7. These are used to short out the secondary of the CTs prior to equipment installation or when servicing them. 

Figure 1.1-7. Example of Differential Circuit with Current Transformer Symbols



To be Continued.......

No comments:

Post a Comment

Medium-Voltage Distribution System Design

A. Single Bus, Figure 1.1-40 The sources (utility and/or generator(s)) are connected to a single bus. All feeders are connected to the ...