Wednesday 19 February 2020

Designing of Distribution System (Part - 4)


Key interlocks are available in a variety of configurations including transfer blocks to capture keys from multiple sources. They are often used as part of Lockout and Tag-Out procedures. It is recommended that the design engineer refer to a key interlock manufacturer such as Kirk or Superior for further documentation and specific operational details. 

Drawing Notes are extremely important as they describe specific functional requirements. In Figure 1.1-12, Note 3 above switchgear “SUS-F1A” describes an additional requirement for a Priority Load Shed Scheme to ensure the generator is not overloaded. The details of this scheme would need to be coordinated with the generator manufacturer and further defined in the switchgear specifications. 

Note 4 calls for DT1150+ electronic breaker trip units that include an Arcflash Reduction Maintenance Mode. This feature limits arc flash energy in compliance with Article 240.87 of the 2014 NEC by using an alternate high-speed analog instantaneous trip setting to reduce arcing time. Note 5 requires a touchscreen panel to monitor the operating variables as well as be used to activate the Arcflash Reduction Maintenance Mode remotely.


Figure 1.1-11. Drawing Notes and Key Interlock Scheme in LV Switchgear

This permits personnel who will be working on the equipment to be in a safe location outside of the arc flash zone when enabling the Arcflash Reduction Maintenance Mode. Note 4 also requires Zone Selective Interlocking. This feature permits higher speed tripping of the Main breaker, if it does not receive a restraining signal from a downstream feeder breaker that it is tripping to clear a fault. Note 6 adds a requirement for BACnet communications functionality to a future Building Management System. It also provides a point of demarcation between the scope of work to be provided by the installing contractor and what portion of the wiring and interface will be required of the BMS vendor. Each of the circuit breaker symbols in the
“SUS-F1A” switchgear are surrounded by double arrows signifying that these breakers are drawout versus fixed mount. Additionally, the “E.O.” nomenclature in the middle of the breaker symbol represents “Electrically Operated”. This function makes it easier to open and close the breaker. It also enables the opportunity for remote control from a handheld pendant operating station or a wall-mounted control panel.

Each circuit breaker is named and its Frame Size (AF), Trip Rating (AT) and protective functions such as Long, Short and Ground (LSG) or Long, Short, Instantaneous and Ground (LSIG) are noted accordingly. Since this equipment is drawout UL 1558 switchgear, the 4 cell high structure number and associated breaker cell are illustrated. 

“Spare” breakers have been located in the top “A” cells 02A and 04A as well as cells 04B and 4C in structure #4. The generator breaker is also located in top cell 03A of structure #3, for cable and conduit egress out the top. In this example, all other breaker cables “feeding loads exit out the bottom of the switchgear. This avoids bottom exiting cables from covering access to the lugs for the spare and generator breakers. Consequently, it permits room to terminate the future cables, coming into the top of the switchgear, easily at a later date. 

It is always wise to include spare breakers of important frame and trip sizes in a drawout switchgear lineup. These spare breakers can either allow for future load growth or provide a readily available backup that can be used in the event that an active breaker requires maintenance or service. 

Note that interference interlocks are supplied on breakers and in switchgear compartments where the compartments are of the same physical size. This rejection feature ensures that an insufficient short circuit or incorrect ampacity rated breaker cannot be inserted into the wrong size cell.

Figure 1.1-12. Drawing Notes and Key Interlock Scheme in LV Switchgear

As an example, a 1600 A breaker cannot be used in a cell configured for 800 A as it would not likely protect the cell bus runbacks and outgoing cables appropriately. Likewise, a 65 kA short circuit rated breaker could not be inserted into a switchgear cell rated for 85 kA.

Figure 1.1-12 shows the main bus for the switchgear rated at 4000 A with an 85 kA short-circuit rating. A busway symbol is illustrated above the tie breaker, indicating that it is connecting to the other half of a double-ended switchgear lineup. 

Eaton’s low-voltage busway can be supplied in ratings of 6–30 cycles. The 4000 A busway shown has a 200 kA 6 cycle rms symmetrical short-circuit rating that exceeds the 85 kA rating of the “SUS-F1A” switchgear bus on the drawing.

The calculated short-circuit rating required for the “SUS-F1A” switchgear is dependent on a number of factors including: the available short circuit upstream, the inclusion of the cable and transformer impedances feeding it, as well as the short-circuit contribution from the motors downstream. 

In actuality, the short circuit current available may be lower than the 85 kA shown on the drawing, permitting a potential cost and space savings, if the rating required is dropped to 65 kA or below. A short circuit study would need to be done to confirm this.

Consequently, it is very important to indicate the actual breaker short-circuit rating as well as the switchgear bus ratings on the One-Line. These also need to be consistent with other schedules and drawings, as well as in the equipment specifications. This can prevent a bidder from incorrectly quoting 85 kA rated switchgear with 65 kA rated breakers. 

The System One-Line shows the incoming surge protective device (SPD) in “SUS-F1A” is rated at 250 kA per phase. As shown in Figure 1.1-13, SPDs in the other downstream equipment are rated at 120 kA per phase. This surge protection scheme as shown is applied in a tiered approach per the IEEE Emerald Book. In this arrangement, the highest level of surge protection is at the incoming source. Downstream switchboards or panelboards closer to the loads provide the next of surge protection. 

There is a considerable amount of distribution equipment illustrated on the example System One-Line. For that reason, reference is made to other drawings and schedules that would comprise the hypothetical bid package. As an example, 1600 A distribution switchboard DSB DF4A has a note to see schedule DSB-DF4A for the end loads. The same is true for power panel PP-DF6A.

Figure 1.1-13. Distribution Equipment Downstream of the SUS-P1A Switchgear


No comments:

Post a Comment

Medium-Voltage Distribution System Design

A. Single Bus, Figure 1.1-40 The sources (utility and/or generator(s)) are connected to a single bus. All feeders are connected to the ...